P0263 – Function of Digital Input DI1
P0264 – Function of Digital Input DI2
P0265 – Function of Digital Input DI3
P0266 – Function of Digital Input DI4
P0267 – Function of Digital Input DI5
P0268 – Function of Digital Input DI6
P0269 – Function of Digital Input DI7
P0270 – Function of Digital Input DI8
Adjustable
0 to 25
Range:
Properties:
cfg
Access groups
I/O
via HMI:
Description:
These parameters allow configuring the digital input function, according to the adjustable range listed in
12.8: Digital input functions on page
Value
0
Not Used
1
Run/Stop Command
2
General Enable Command
3
Quick Stop Command
4
Forward/Reverse
5
Local/Remote Selection
6
JOG
7
SoftPLC
8
2
Ramp Selection
nd
9
Not Used
10
Not Used
11
Not Used
12
No External Alarm
13
No External Fault
14
Reset
15
Disab. Flying-Start
16
Not Used
17
Lock Programming
18
Load User 1
19
Load User 2
20
Auto/Man main PID (1)
21
Auto/Man external PID (1)
22
Not Used
23
Bypass Mode
24
Activate Fire Mode
25
PTC
(1) For digital inputs DI5, DI6, DI7 and DI8, those options do not present associated functions.
Digital and Analog Inputs and Outputs
12-17.
Table 12.8: Digital input functions
Description
Factory
P0263 = 1
P0264 = 0
Setting:
P0265 = 20
P0266 = 21
P0267 = 0
P0268 = 0
P0269 = 0
P0270 = 0
Dependence
-
P0224 = 1 or P0227 = 1
P0224 = 1 or P0227 = 1
P0224 = 1 or P0227 = 1
P0223 = 4 or P0226 = 4
P0220 = 4
P0225 = 2 or P0228 = 2
Prog. SoftPLC
P0105 = 2
-
-
-
-
-
Active fault
P0320 = 1 ou 3
-
-
Inverter disabled
Inverter disabled
-
-
-
-
-
-
CFW501 | 12-17