P1062 – Process Variable of the External PID Controller
Adjustable
-32768 to 32767
Range:
Properties:
ro
Access groups
HVAC
via HMI:
Description:
This parameter shows the actual value of the process variable of the main PID controller in engineering unit.
NOTE!
This parameter is displayed as the selection in the indirect engineering unit 2 parameters (P0512
and P0513).
P1063 – External PID Controller Output
Adjustable
0.0 to 100.0 %
Range:
Properties:
ro
Access groups
HVAC
via HMI:
Description:
This parameter indicates the actual value of External PID controller output.
P1064 – External PID Controller Action Control
Adjustable
0 = Disable PID
Range:
1 = Direct Mode
2 = Reverse Mode
Properties:
cfg
Access groups
HVAC
via HMI:
Description:
This parameter defines how the action control or regulation of External PID controller.
P1064
0
It defines the External PID controller 1 will be disabled to operation.
1
It defines the External PID controller 1 action control or regulation will be enabled in direct mode.
2
It defines the External PID controller 1 action control or regulation will be enabled in reverse mode.
NOTE!
In situations that, in order to increase the value of the process variable, it is necessary to increase the output
of the PID controller, the control action of the external PID controller must be set to direct mode. E.g.: Valve
installed in a tank water input. For the level of the tank (process variable) to increase, it is necessary that the
flow increase, which is accomplished by opening the valve. In situations that, in order to increase the value
of the process variable, it is necessary to decrease the output of the PID controller, the control action of
the external PID controller must be set to reverse mode. E.g.: Valve installed in a tank water output. For the
level of the tank (process variable) to increase, it is necessary that the flow decrease, which is accomplished
by closing the valve.
Table 18.8: Description of External PID controller action control
Description
HVAC Functions
Factory
Setting:
Factory
Setting:
Factory
0
Setting:
CFW501 | 18-21