WEG CFW501 V1.8X Programming Manual page 64

Frequency inverter
Table of Contents

Advertisement

Logical Command and Speed Reference
P0223 – Direction of Rotation Selection – LOCAL Situation
P0226 – Direction of Rotation Selection – REMOTE Situation
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
These parameters define the origin source for the "Direction of Rotation" command in the Local and Remote
situation, where:
H: it means clockwise default at the inverter power-up.
7
AH: means counterclockwise default at the inverter power-up.
DIx: refer to
section 12.5 DIGITAL INPUTS on page
P0224 – Run / Stop Selection – LOCAL Situation
P0227 – Run / Stop Selection – REMOTE Situation
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
These parameters define the origin source for the "Run/Stop" command in the Local and Remote situation. This
command corresponds to the functions implemented in any of the command sources able to enable the motor
movement, that is, general enable, ramp enable, turn on, turn off, JOG, etc.
7-6 | CFW501
0 = Clockwise
1 = Counterclockwise
2 = HMI Key (H)
3 = HMI Keys (AH)
4 = DIx
5 = Serial / USB (H)
6 = Serial / USB (AH)
7 = SoftPLC
cfg
I/O
0 = HMI Keys
1 = DIx
2 = Serial / USB
3 = SoftPLC
cfg
I/O
12-15.
Factory
P0223 = 2
Setting:
P0226 = 0
Factory
P0224 = 0
Setting:
P0227 = 1