Digital and Analog Inputs and Outputs
P0251 – Output Function AO1
P0254 – Output Function AO2
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
These parameters set the analog output functions, according to function and scale presented in
scale of analog outputs on page
Function
12
Constant K is defined based on parameter P0296, according to the table below:
12-8 | CFW501
0 = Speed Ref.
1 = Not Used
2 = Real Speed
3 = Not Used
4 = Not Used
5 = Output Current
6 = Active Current
7 = Output Power
8 = Not Used
9 = Motor Torque
10 = SoftPLC
11 = Not Used
12 = Motor Ixt
13 = P0696 Value
14 = P0697 Value
15 = Not Used
16 = External PID Output
17 = Not Used
18 = P0698 Value
I/O
12-8.
Table 12.3: Full scale of analog outputs
Description
0
Speed reference in the ramp input (P0001)
2
Real speed in the inverter output (P0002)
5
Total output current in rms
6
Active current
7
Output Power
9
Torque on the motor in relation to the rated torque
10
SoftPLC scale for analog output
12
Motor Ixt overload (P0037)
13
Value of P0696 for analog output AOx
14
Value of P0697 for analog output AOx
16
External PID output (P1063)
18
Value of P0698 for analog output AOx
Table 12.4: Constant K defined in parameter P0296
P0296
Constant K
0
240
1
480
2
600
Factory
P0251 = 16
Setting:
P0254 = 5
Table 12.3: Full
Full Scale
P0134
P0134
2xP0295
2xP0295
1.5 x √3 x P0295 x K
200.0 %
32767
100 %
32767
32767
100 %
32767