WEG CFW501 V1.8X Programming Manual page 102

Frequency inverter
Table of Contents

Advertisement

Functions Common to all the Control Modes
P0135 – Maximum Output Current
Adjustable
Range:
Properties:
Access groups
via HMI:
Description:
Current level to activate the current limitation for the ramp hold and decelerate ramp modes, as per
(a) and (b) Actuation modes of current limitation via P0135 on page
11
11-8 | CFW501
0.0 to 200.0 A
V/f, V V W
BASIC, MOTOR
Motor
current
P0135
Output
speed
Ramp
acceleration
(P0100)
Acceleration
Motor
current
P0135
Output
speed
deceleration
Figure 11.6: (a) and (b) Actuation modes of current limitation via P0135
11-8, respectively.
Motor
current
P0135
t(s)
Ramp
deceleration
(P0101)
t(s)
Deceleration
(a) "Ramp Hold "
t(s)
Ramp
(P0101)
t(s)
(b) "Ramp Deceleration"
Factory
1.5 x I
nom
Setting:
Figure 11.6:
t(s)
t(s)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents