WEG CFW501 V1.8X Programming Manual page 93

Frequency inverter
Table of Contents

Advertisement

For better visualization of the start-up in the V V W mode, check
10-10, below.
Seq
Action/Indication on the Display
1
Monitoring mode.
Press the ENTER/MENU key to enter the 1
programming mode.
2
The PARAM group is selected; press the
until selecting the STARTUP group.
3
When the STARTUP group is selected, press the
ENTER/MENU key.
4
Press ENTER/MENU and with the
set the value 3, which activates V V W control mode.
5
Press ENTER/MENU to save the modification of P0202.
11
If necessary, modify the content of P0403 – Motor rated
frequency, or press the
12
If necessary, modify the content of P0404 – Motor rated
power, or press the
level of the
st
or
key
and
keys
key for the next parameter.
key for the next parameter.
Figure 10.2: Start-up of the VVW mode on page
Seq
Action/Indication on the Display
6
Press the
key to proceed with the Startup of the V V W.
7
If necessary, modify the content of P0399 – Motor rated
efficiency, or press the
8
If necessary, modify the content of P0400 – Motor rated voltage
or press the
key for the next parameter.
9
If necessary, modify the content of P0401 – Motor rated
current, or press the
10
If necessary, modify the content of P0402 – Motor rated
speed, or press the
16
At the end of the Self-Tuning. The values of P0408
automatically return to "0", as well as the "RUN" and
"CONF" status are erased.
Press the
key for the next parameter.
17
The result of the Self-Tuning is the value in ohms of the stator
resistance shown in P0409. This is the last parameter of
the Self-Tuning of the VVW control mode. Pressing the
key returns to the initial parameter P0202.
V V W Vector Control
key for the next parameter.
key for the next parameter.
key for the next parameter.
CFW501 | 10-9
10

Hide quick links:

Advertisement

Table of Contents
loading