WEG CFW501 V1.8X Programming Manual page 151

Frequency inverter
Table of Contents

Advertisement

P0007 – Output Voltage
Adjustable
0 to 2000 V
Range:
Properties:
ro
Access groups
READ
via HMI:
Description:
It indicates the line voltage in inverter output, in Volts (V).
P0009 – Motor Torque
Adjustable
-1000.0 % to 1000.0 %
Range:
Properties:
ro
Access groups
READ
via HMI:
Description:
It indicates the torque developed by the motor in relation to the rated torque.
P0010 – Output Power
Adjustable
0.0 to 6553.5 kW
Range:
Properties:
ro
Access groups
READ
via HMI:
Description:
It indicates the electric power in the inverter output. This power is determined through the formula:
P0010 = √3 x P0003 x P0007 x P0011.
Where:
P0003 is the output current measured;
P0007 is the reference output voltage (or estimated);
P0011 is the value of the cosine [(vector angle of the reference output voltage) – (vector angle of the output
current measured)].
P0011 – Cos φ on the Output
Adjustable
-1.00 to 1.00
Range:
Properties:
ro
Access groups
READ
via HMI:
Description:
It indicates the power factor, that is, the relationship between the real power and the total power absorbed by
the motor.