Digital Inputs - WEG CFW501 V1.8X Programming Manual

Frequency inverter
Table of Contents

Advertisement

P0258 – Frequency Output Gain FO
Adjustable
0.000 to 9.999
Range:
P0259 – Minimum Frequency Output FO
Adjustable
10 to 20000 Hz
Range:
P0260 – Maximum Frequency Output FO
Adjustable
10 to 20000 Hz
Range:
Properties:
Access groups
I/O
via HMI:
Description:
Gain, minimum and maximum values for frequency output FO.

12.5 DIGITAL INPUTS

In order to use the digital inputs, the CFW501 features up to eight ports, depending on the plug-in module connected
to the product. Check
Table 12.1: I/O Configurations of the CFW501 on page
Below is a detailed description of the parameters for digital inputs.
P0271 – Digital Input Signal
Adjustable
0 = All DIx are NPN
Range:
1 = (DI1) - PNP
2 = (DI1..DI2) - PNP
3 = (DI1..DI3) - PNP
4 = (DI1..DI4) - PNP
5 = (DI1..DI5) - PNP
6 = (DI1..DI6) - PNP
7 = (DI1..DI7) - PNP
8 = All DIx are PNP
Properties:
cfg
Access groups
I/O
via HMI:
Description:
It configures the default for the digital input signal, that is, NPN and the digital input is activated with 0 V, PNP
and the digital input is activated with +24 V.
Digital and Analog Inputs and Outputs
Factory
Setting:
Factory
Setting:
12-1.
Factory
Setting:
1.000
10 Hz
Factory
10000 Hz
Setting:
0
CFW501 | 12-15
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents