WEG CFW501 V1.8X Programming Manual page 69

Frequency inverter
Table of Contents

Advertisement

P0690 – Logical Status 2
Adjustable
0000h to FFFFh
Range:
Properties:
ro
Access groups
NET, READ
via HMI:
Description:
Parameter P0690 presents other signaling bits for functions exclusively implemented in the CFW501. The
function of each bit of P0690 is described in
BIT
Function
0 to 3
Reserved
4
Fs reduction
5
Sleep State
6
Deceleration Ramp
7
Acceleration Ramp
8
Freeze Ramp
9
Setpoint Ok
10
DC link regulation
Configuration in
11
50 Hz
12
Ride-Through
13
Flying-Start
14
DC Braking
15
PWM Pulses
Logical Command and Speed Reference
Table 7.4: Status word (P0680) on page
Table 7.4: Status word (P0680)
0: Output frequency reduction inactive.
1: Output frequency reduction active.
0: No deceleration.
1: Inverter decelerating.
0: No acceleration.
1: Inverter accelerating.
0: Ramp operating in normal conditions.
1: The path of the ramp is frozen by some command source or internal function..
0: Output frequency has not reached reference yet.
1: Output frequency reached reference.
0: DC link regulation or current limitation inactive.
1: DC link regulation or current limitation active (P0150).
0: Factory default loaded in 1800 rpm / 60 Hz (P0204 = 5).
1: Factory default loaded in 1500 rpm / 50 Hz (P0204 = 6).
0: No execution of Ride-Through.
1: Executing Ride-Through.
0: No execution of Flying Start.
1: Executing Flying Start.
0: DC breaking inactive.
1: DC breaking active.
0: PWM voltage pulses in the output disabled.
1: PWM voltage pulses in the output enabled.