WEG CFW501 V1.8X Programming Manual page 190

Frequency inverter
Table of Contents

Advertisement

HVAC Functions
DIx/Fault
N
DOx
drive
DOx
Line
P0006
P0680
An example of connecting the bypass can be seen in
used in this example:
P0268 = 23 (DI6 = Bypass Mode)
P0275 = 39 (RL1 = Drive Bypass Contactor)
P0276 = 40 (RL2 = Mains Bypass Contactor)
P0583 = 1 (Bypass Enabled by DIx)
P0584 = 0.30 s
18
18-32 | CFW501
Bypass
t
desm
P0584
Figure 18.2: Bypass mode activation logic
~
CFW501
RUN
t
P0584
desm
Figure 18.3: Bypass mode example on page
M