WEG CFW501 V1.8X Programming Manual page 99

Frequency inverter
Table of Contents

Advertisement

P0151 – Actuation Level of the DC Link Voltage Regulation
Adjustable
339 to 1200 V
Range:
Properties:
V/f, V V W
Access groups
MOTOR
via HMI:
Description:
Voltage level to activate the DC Link Voltage regulation.
P0152 – Gain Proportional to the DC Link Voltage Controller
Adjustable
0.00 to 9.99
Range:
Properties:
V/f, VVW
Access groups
MOTOR
via HMI:
Description:
Gain proportional to the DC link voltage controller.
When the option of P0150 is 1 or 3, the value of P0152 is multiplied by the "error" of the DC link voltage, seeing
that the error results from the difference between the actual DC link voltage (P0004) and the actuation level
of the DC link voltage regulation (P0151). The result is added directly to the inverter output speed in rpm. This
resource is normally used to prevent overvoltage in applications with eccentric loads.
Figure 11.2: Block diagram DC link voltage limitation – Ramp Hold (P0152 = 0 or P0152 = 2) on page 11-5
Figure 11.5: Example graph of the DC ling voltage limitation – Accelerate Ramp (P0152 = 1 or P0152 = 3) on
page 11-7
show the block diagrams and example graphs.
P0001
P0004
Figure 11.2: Block diagram DC link voltage limitation – Ramp Hold (P0152 = 0 or P0152 = 2)
Functions Common to all the Control Modes
Ramp
P0100-P0104
Reference
Hold
Error
≥ 0
+
-
P0151
Factory
Setting:
Factory
Setting:
Output speed
P0002
400 V
(P0296 = 0)
800 V
(P0296 = 1)
1000 V
(P0296 = 2)
1.50
to
11
CFW501 | 11-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents