WEG CFW501 V1.8X Programming Manual page 105

Frequency inverter
Table of Contents

Advertisement

P0300 – DC Braking Time at Stop
Adjustable
0.0 to 15.0 s
Range:
Properties:
Access groups
MOTOR
via HMI:
Description:
DC braking duration at the start.
Stop (b) General Enable on page 11-11
de-magnetization of the motor can be observed. This time is proportional to the speed at the moment of the
injection of direct current.
Output
P0300
speed
P0301
Active
DIx - Run / Stop
Inactive
(a)
Figure 11.9: (a) and (b): Actuation of DC braking at command stop (a) Run/Stop (b) General Enable
During the braking process, if the inverter is enabled, the braking is interrupted and the inverter will start
operating normally.
ATTENTION!
The DC braking can continue acting even if the motor has already stopped. Be careful with the thermal
dimensioning of the motor for short-period cyclic braking.
Functions Common to all the Control Modes
Injection of direct
current at starting
Output speed
P0299
DC Braking
Run
Stop
Figure 11.8: DC braking actuation at start
Figure 11.9: (a) and (b): Actuation of DC braking at command stop (a) Run/
shows the braking behavior at the stop, where the dead time for the
Injection of
DC current
Output
speed
Time
Active
DIx - General enable
Time
P0302
Time
P0300
Dead
time
Inactive
(b)
Factory
0.0 s
Setting:
Time
CFW501 | 11-11
11