12.4 FREQUENCY OUTPUT

Like the frequency input is implemented in the digital input DI2, the frequency output is fixed to the transistor
digital output DO2.
The configuration and resources available in the frequency output are basically the same as those of analog
outputs, as shown in
Figure 12.5: Block diagram of the output in frequency FO (DO2) on page
Function
FO – P0257
P0001
P0002
P0003
P0011
P0009
SoftPLC
P0037
P0696
P0697
P0698
(*) Control terminal available in the Plug-In module.
P0016 – Frequency Output Value FO in %
Adjustable
0.0 to 100.0 %
Range:
Properties:
ro
Access groups
READ, I/O
via HMI:
Description:
The percentage value of the output frequency FO. This value is given in relation to the range defined by P0259
and P0260.
P0017 – Frequency Output Value FO in Hz
Adjustable
0 to 20000 Hz
Range:
Properties:
ro
Access groups
READ, I/O
via HMI:
Description:
The value in hertz of the output frequency FO.
Calc. Hz/%
(%)
100
P0259
Gain
FO – P0258
Figure 12.5: Block diagram of the output in frequency FO (DO2)
Digital and Analog Inputs and Outputs
FO(Hz)
Value FO
P0260
(Hz)
FO(%)
FO(Hz) – P0017
FO(%) – P0016