WEG CFW501 V1.8X Programming Manual page 136

Frequency inverter
Table of Contents

Advertisement

Rheostatic Braking
Steps to enable the rheostatic braking:
With the inverter powered down, connect the braking resistor (refer to the user's manual, item 3.2 - Electric
Installations).
Setting P0151 for the maximum value: 410 V (P0296 = 0), 810 V (P0296 = 1) or 1200 V (P0296 = 2), according
to the situation, in order to prevent the actuation of the DC link voltage regulation before the rheostatic braking.
DANGER!
Be sure the inverter is OFF before handling the electric connections and read carefully the installation
instructions of the user's manual.
13
13-2 | CFW501
DC link voltage (U
P0153
U
rated
d
Braking resistor
voltage (BR)
Figure 13.1: Rheostatic braking actuation curve
) (P0004)
d
F0022 - Overvoltage
Rheostatic braking
actuation
Time
U
U
d
d
Time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents