WEG CFW501 V1.8X Programming Manual page 25

Frequency inverter
Table of Contents

Advertisement

Fault / Alarm
A0046
Motor overload alarm.
Motor overload
A0047
Overload alarm on the power pack with
IGBT overload
IGBTs.
A0050
Overtemperature alarm from the power
Power module
module temperature sensor (NTC).
overtemperature
A0090
External alarm via DIx (option "Without
External alarm
External Alarm" in P0263 to P0270).
A0128
Alarm that indicates serial communication
Telegram reception
fault. It indicates the equipment stopped
timeout
receiving valid serial telegrams for a
period longer than the setting in P0314.
A0213
Alarm that indicates the short cycle
Protection Against Short
protection occurred.
Cycles
A0700
No communication with remote HMI, but
Communication fault with
there is no speed command or reference
remote HMI
for this source.
A0702
This failure occurs when there is a
Inverter disabled
SoftPLC movement block (REF block)
active and the "General Enable"
command is disabled.
A0704
It occurs when 2 or more SoftPLC
Two movem. enabled
movement blocks (REF Block) are
enabled at the same time.
A0706
This failure occurs when a SoftPLC
Refer. Not Progr. SPLC
movement block is enabled and the
speed reference is not programmed for
the SoftPLC.
A0710
It occurs when you try to download to
SPLC Progr. Bigger than
the inverter a SoftPLC Program that is
8 KB
too large (larger than 8 KB).
A0750
Alarm that indicates an analog input was
Program AIx for Process
not programmed for the process variable
Variable of
of the main PID controller.
Main PID Controller
A0752
Alarm that indicates a digital input was
Program DIx for Automatic
not programmed for automatic / manual
/ Manual Selection of the
selection of the main PID controller.
Main PID Controller
A0754
Alarm that indicates the origin of the
Program LOCAL
speed reference in LOCAL mode was not
Reference (P0221) for
programmed for SoftPLC.
SoftPLC
A0756
Alarm that indicates the origin of the speed
Program REMOTE
reference in REMOTE mode was not
Reference (P0222) for
programmed for SoftPLC.
SoftPLC
A0758
Alarm that indicates the parameter for
Program Indirect
engineering unit of the motor speed was
Engineering Unit 4 (P0516)
not programmed for Hz or rpm.
for Hz or rpm
Quick Reference of Parameters, Alarms and Faults
Description
Possible Causes
Settings of P0156, P0157, and P0158 are too low for the
used motor.
Overload on the motor shaft.
Inverter output overcurrent.
High ambient temperature around the inverter (>50 °C (> 122 °F))
and high output current.
Blocked or defective fan.
Heatsink is too dirty, preventing the air flow.
Wiring on DI1 to DI8 inputs are open or have poor contact.
Check network installation, broken cable or fault/poor contact
on the connections with the network, grounding.
Ensure the master always sends telegrams to the equipment
in a time shorter than the setting in P0314.
Disable this function in P0314.
The STAR command occurred during the time count defined
by P0587.
The STOP command occurred during the time count defined
by P0586.
Check if the communication interface with the HMI is properly
configured in parameter P0312.
HMI cable disconnected.
Check if the drive general enable command is active.
Check the user's program logic.
Check the programming of the references in the local and/or
remote mode (P0221 and P0222).
Extension of the SoftPLC Prog. exceeded 8 KBytes.
Parameter P0231 or P0236 was not programmed for 5 or 6.
Parameter P0263 or P0264 or P0265 or P0266 was not
programmed for 20.
Main PID controller is enabled (P1017 in 1 or 2) and the
CFW501 frequency inverter is running the motor in LOCAL
mode and parameter P0221 is not programmed for 7.
Main PID controller is enabled (P1017 in 1 or 2) and the
CFW501 frequency inverter is running the motor in REMOTE
mode and parameter P0222 is not programmed for 7.
Parameter P0516 was not programmed for 13 (Hz) or 3 (rpm).
0
0
CFW501 | 0-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents