Value
Output Function
0
Not Used
1
N* > Nx
2
N > Nx
3
N < Ny
4
N = N*
5
Zero Speed
6
Is > Ix
7
Is < Ix
8
Torque > Tx
9
Torque < Tx
10
Remote
11
Run
12
Ready
13
No Fault
14
No F0070
15
Not Used
16
No F0021/22
17
No F0051
18
No F0072
19
4-20 mA OK
20
P0695 Value
21
Clockwise
22
Ride-Through
23
Pre-Load OK
24
With Fault
25
Hours Enab > Hx
26
SoftPLC
27
Not Used
28
F > Fx(1)
29
F > Fx(2)
30
Not Used
31
Not Used
32
No Alarm
33
No F/A
34
F/A Dry Pump
35
F/A Broken Belt
36
F/A Filter maintenance
37
Sleep Mode
38
Not Used
39
Drive Bypass Contactor
40
Mains Bypass Contactor
41
Fire Mode
42
Self-tuning
NOTE!
Refer to
chapter 18 HVAC FUNCTIONS on page 18-1
and 41.
Table 12.9: Digital output functions
Digital output inactive.
Active when the speed reference (P0001) is greater than Nx (P0288).
Active when the motor speed (P0002) is above Nx (P0288) plus a hysteresis value (P0287) and inactive
when the motor speed (P0002) is below Nx (P0288) minus a hysteresis value (P0287).
Active when the motor speed (P0002) is above Ny (P0289) plus a hysteresis value (P0287) and inactive
when the motor speed (P0002) is below Ny (P0289) minus a hysteresis value (P0287).
Active when the motor speed (P0002) is equal to the seep set in P0292.
Motor speed is below the value set in P0291.
Active if the output current Is (P0003) > Ix (P0290).
Active if the output current Is (P0003) < Ix (P0290).
Active if the motor torque T (P0009) > Tx (P0293).
Active if the motor torque T (P0009) < Tx (P0293).
Active if the command is the remote condition (REM).
Active if the motor is running (active output PWM pulses) RUN status.
Active if the inverter has no fault.
Active if the inverter has no fault.
Active if the inverter has no overcurrent fault (F0070).
Digital output inactive.
Active if the inverter has no overvoltage or undervoltage fault (F0022 or F0021).
Active if the inverter is without IGBT overtemperature fault (F0051).
Active if the inverter is without motor overload fault (F0072).
Active if AIx is set for 4 to 20 mA (P0233 and/or P0238 and/or P0243 equal to 1 or 3) and AIx < 2 mA.
Status of the bits 0 to 4 of P0695 activate digital outputs DO1 to DO5, respectively.
Active if the inverter direction of rotation is Clockwise.
Active if the inverter is executing the Ride-Through function.
Active if the pre-load relay of the DC link capacitors was already activated.
Active if the inverter has a fault.
Active when Time Enabled (P0043) is above Hx (P0294).
Activates DOx output according to the SoftPLC memory area. Read the SoftPLC User's Manual.
Digital output inactive.
Active when the output frequency F (P0005) is above Fx (P0281) plus a hysteresis value (P0282) and
inactive when F (P0005) is below Fx (P0281) minus a hysteresis value (P0282).
Active when the output frequency F (P0005) is above Fx (P0281) and inactive when F (P0005) is
below Fx (P0281) minus a hysteresis value (P0282).
Digital output inactive.
Digital output inactive.
Active when the inverter has no alarm.
Active when the inverter is without alarm and without fault.
Active when dry pump condition was detected (A0766/F0767).
Active when broken belt condition was detected (A0768 / F0769).
Active when the filter maintenance condition was detected (A0770 / F0771).
Active when the inverter has the sleep mode active (A0764).
Digital output inactive.
Digital output inactive.
Digital output inactive.
Digital output inactive.
Active when the inverter is performing the self-tuning function.
Digital and Analog Inputs and Outputs
Description
for further information on options 34, 37, 39
12
CFW501 | 12-23