WEG CFW501 V1.8X Programming Manual page 139

Frequency inverter
Table of Contents

Advertisement

P0349 – Level for Alarm Ixt
Adjustable
70 to 100 %
Range:
Properties:
cfg
Description:
This parameter defines the level for alarm actuation of the motor overload protection (A0046 when P0037 >
P0349). The parameter is expressed in percentage of the overload integrator limit value, where fault F0072
occurs. Therefore, by setting P0349 at 100 %, the overload alarm is inactive.
P0037 – Overload of Motor Ixt
Adjustable
0 to 100 %
Range:
Properties:
ro
Access groups
READ
via HMI:
Description:
This parameter indicates the present motor overload percentage or overload integrator level. When this
parameter reaches the P0349 value the inverter will indicate the motor overload alarm (A0046). As soon as the
value of the parameter is at 100 %, a motor overload fault (F0072) is raised.
3
2.5
2
1.5
1
0.5
0
0
Region of overload
60
120
Time(s)
Figure 14.1: Actuation of the motor overload
Faults and Alarms
Factory
Setting:
Factory
Setting:
180
240
85 %
14
300
CFW501 | 14-3