P0513 – Indirect Indication Form 2
Adjustable
0 = wxyz
Range:
1 = wxy.z
2 = wx.yz
3 = w.xyz
Properties:
Access groups
HMI
via HMI:
Description:
This parameter selects the decimal point that will be viewed in the user's parameter of the SoftPLC which is
associated to it, that is, any user's parameter of the SoftPLC that is associated to the indirect indication form 2
will be viewed in this format on the CFW501 HMI.
NOTE!
Parameters P1011, P1015, P1027, P1028, P1031 and P1033 of the main PID controller (HVAC
functions) are associated to the indirect indication form 2.
P0516 – Indirect Engineering Unit 4
Adjustable
0 = none
Range:
1 = V
2 = A
3 = rpm
4 = s
5 = ms
6 = none
7 = m
8 = none
9 = none
10 = %
11 = °C
12 = none
13 = Hz
14 = none
15 = h
16 = W
17 = kW
18 = none
19 = none
20 = min
21 = °F
22 = bar
23 = mbar
24 = psi
25 = Pa
26 = kPa
27 = MPa
28 = mwc (meter of water column)
29 = mca (metro de coluna d'água)
30 = gal
31 = l (litro)
32 = in
33 = ft
Basic Instructions for Programming and Settings
Factory
1
Setting:
Factory
13
Setting:
CFW501 | 5-9