Evaporator Flow Switch Status

Keypad Menu Path:
This output network variable indicates the status of water flow through the evaporator. (D7)
No Keypad Equivalent
Measurement
Flow State
BACnet
Variable Details
Object Type
Binary Input
LONWORKS
Variable Details
LONWORKS Name
nvoChWFlow
Structure
typedef struct {
unsigned
value;
signed
state;
} SNVT_switch;
Valid Range
Value Field
unused
State Field
0
No Flow
1
Flow
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Units
BACnet: Enumerated
NA
LONWORKS: Structure
Object Identifier
Type Enumeration
3
EvapWaterFlowStatus
Property Values
0 = No Flow(Inactive)
1 = Flow(Active)
Profile
Proprietary
Data Type
Valid Range
Instance
Property Name
34
Present Value
Object Name
SNVT Type
SNVT Index
switch