Table 5: LONWORKS Alarm Messages
Alarm Description
0
(reserved)
Entering Condenser Water Temperature Sensor
1
Fault
Entering Evaporator Water Temperature Sensor
2
Fault
3
Liquid Line Refrigerant Temperature Sensor Fault
Leaving Condenser Water Temperature Sensor
4
Fault
5
Repower After Power Loss #1
6
Repower After Power Loss #2
7
Repower After Power Loss #3
9
Expansion Alarm - WARNING
10
Low Ambient Temperature Lockout
High Condenser Pressure - Inhibit Loading Circuit
11
#1
High Condenser Pressure - Inhibit Loading Circuit
12
#2
High Condenser Pressure - Inhibit Loading Circuit
13
#3
15
High Condenser Pressure - Unload
16
High Condenser Pressure - Unload Circuit #1
17
High Condenser Pressure - Unload Circuit #2
18
High Condenser Pressure - Unload Circuit #3
20
Condenser Water Freeze Protect Comp #1
21
Condenser Water Freeze Protect Comp #2
22
Condenser Pump #1 Fault
23
Condenser Pump #2 Fault
24
High Discharge Temperature Comp #1
25
High Discharge Temperature Comp #2
Entering Evap Temperature Sensor Fault (EWT
26
reset active)
27
Low Evaporator Pressure - Inhibit Loading
Low Evaporator Pressure - Inhibit Loading Circuit
30
#1
Low Evaporator Pressure - Inhibit Loading Circuit
31
#2
Low Evaporator Pressure - Inhibit Loading Circuit
32
#3
34
Low Evaporator Pressure - Unload
35
Low Evaporator Pressure - Unload Circuit #1
36
Low Evaporator Pressure - Unload Circuit #2
37
Low Evaporator Pressure - Unload Circuit #3
39
High Motor Current On Compressor #1
40
High Motor Current On Compressor #2
44
Evaporator Freeze Protect Comp #1
45
Evaporator Freeze Protect Comp #2
46
Evaporator Pump #1 Fault
47
Evaporator Pump #2 Fault
49
Outside Ambient Temperature Sensor Fault
50
Compressor Current Overload Trip #1
1-AGS 'C' Vintage Only (two circuits only)
2-AGS 'B' Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8-Should be "No Start - Interlock Switch" on WMC chillers.
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
LonTalk Message
WARN-Ent Cond Temp Sensor Fail
WARN-Ent Evap Temp Sensor Fail
WARN-Liq Line Temp Sensor Fail
WARN-Lvg Cond Temp Sensor Fail
WARN-Pwr Loss While Running #1
WARN-Pwr Loss While Running #2
WARN-Pwr Loss While Running #3
WARNING(Check Unit for Detail)
NO START - Ambient Temp Low
NO LOAD - Cond Press High #1
NO LOAD - Cond Press High #2
NO LOAD - Cond Press High #3
UNLOAD - Cond Press High
UNLOAD - Cond Press High #1
UNLOAD - Cond Press High #2
UNLOAD - Cond Press High #3
PUMP ON - Cond Water Freeze #1
PUMP ON - Cond Water Freeze #2
PUMP 2 ON - Cond Pump Fail #1
PUMP 1 ON - Cond Pump Fail #2
LOAD - Discharge Temp High #1
LOAD - Discharge Temp High #2
NO RESET-Evap EWT Sensor Fail
NO LOAD - Evap Press Low
NO LOAD - Evap Press Low #1
NO LOAD - Evap Press Low #2
NO LOAD - Evap Press Low #3
UNLOAD - Evap Press Low
UNLOAD - Evap Press Low #1
UNLOAD - Evap Press Low #2
UNLOAD - Evap Press Low #3
UNLOAD - Comp Current High #1
UNLOAD - Comp Current High #2
PUMP ON - Evap Water Freeze #1
PUMP ON - Evap Water Freeze #2
START#2 - Evap Pump Fail #1
START#1 - Evap Pump Fail #2
UNIT STOP-AmbAirTempSensorFail
COMP STOP-Current Overload #1
98
lonWorKs a
WSC,
WDC,
WPV,
HSC,
HDC,
TSC,
WMC,
WCC
AGZ
ACZ
X
X
X
X
X
X
X
X
5
3
X
X
5
3
X
6
X
4
X
5
X
3
X
5
X
3
X
X
X
X
X
X
X
X
X
6
4
X
X
X
5
3
X
X
5
X
3
X
6
X
4
X
X
5
X
3
X
X
5
X
3
X
X
X
X
X
X
X
X
X
m
larm
essages
lonWorKs a
m
larm
essages
WGZ,
TGZ
AGS
WGS
X
X
X
X
X
X
X
X
X
X
X
X
2
X
X
X
X
X
X
X
X
X
X
X
X
2
X
X
X
X
X
X
X
2
X
X
X
X
X
X
X
2
X
X
X
X
X
X
X
2
X
X
X
X
X