Evaporator Leaving Water Temperature for Unit
Keypad Menu Path:
This output network variable indicates the current temperature of the evaporator leaving chilled water. (A6)
Menu
\View
\Unit Water
OR
Menu
\View
Comp (2)
Measurement
Temperature
BACnet
Variable Details
Object Type
Analog Input
LONWORKS
Variable Details
LONWORKS Name
nvoLvgCHWTemp
www.DaikinApplied.com
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
Object Identifier
Type Enumeration
0
LvgEvapWaterTempUnit
Profile
Chiller
Data Type
Valid Range
BACnet: Real
BACnet: -40°–244°F
LONWORKS: -40°–118°C
Instance
Property Name
2
Present Value
Object Name
SNVT Type
SNVT Index
temp_p
63
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
I
eTaIled
aTa
oInT
Default Value
NA
Property Identifier
Property Enumeration
85
SNVT Size
105
two bytes
nformaTIon
Need help?
Do you have a question about the MicroTech II and is the answer not in the manual?
Questions and answers