Chiller Enable

Keypad Menu Path:
This LONWORKS configuration variable sets the default power-up and restart mode of the chiller,
unless the configuration parameter nciDefaults = 1 (See
No Keypad Equivalent
1, the default values are the values specified during manufacturing. Refer to the appropriate Operating
Manual for suitable variable values.
Measurement
Chiller State
LONWORKS
Variable Details
LONWORKS Name
Profile
nciChillerEnable
Chiller
Default Value
0 = Request Chiller Off
The chiller object uses the configuration value of nciChillerEnable on power-up or loss of communication unless the configuration
parameter nciDefaults =1 (See
Structure
typedef struct {
unsigned
value;
signed
state;
} SNVT_switch;
Valid Range
Value Field
unused
State Field
0
Request Chiller Off
1
Request Chiller Auto (run)
0xff
Invalid
www.DaikinApplied.com
Units
NA
LONWORKS: structure
SNVT Type
switch
Default Values on page
59).
Default Values on page
Data Type
Valid Range
Enumerated
SNVT Index
SNVT Size
95
two bytes
27
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
I
eTaIled
aTa
oInT
nformaTIon
59). If nciDefaults =
Default Value
See Below
SCPT_Reference
SCPT_ Index
SCPTpwrUpState
73