Compressor Status
Keypad Menu Path:
This output network variable indicates the number status of the compressor.
No Keypad Equivalent
Measurement
Event Count
BACnet
Compressor Select
This output network variable indicates the compressor status of the compressor selected with
Object Type
Analog Input
Compressor #2
This output network variable indicates the compressor status of the compressor 2. (I105)
Object Type
Analog Input
Compressor #3
This output network variable indicates the compressor status of the compressor 3. (I108)
Object Type
Analog Input
www.DaikinApplied.com
Units
NA
LONWORKS: Fixed Point
Scalar - unsigned long
Object Identifier
Type Enumeration
0
CompressorStatus
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Object Identifier
Type Enumeration
0
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Object Identifier
Type Enumeration
0
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Data Type
Valid Range
BACnet: Real
Instance
Property Name
123
Present Value
Object Name
Instance
Property Name
91
Present Value
Object Name
Comp2Status
Instance
Property Name
99
Present Value
Object Name
Comp3Status
45
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
eTaIled
aTa
oInT
Default Value
0–31
NA
Compressor Select on page
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85
I
nformaTIon
43. (I44)