Heat Recovery Entering Water Temperature
Keypad Menu Path:
This output network variable indicates the current temperature of the water entering the heat recovery
section. (A22)
No Keypad Equivalent
Measurement
Temperature
BACnet
Variable Details
Object Type
Analog Input
LONWORKS
Variable Details
LONWORKS Name
nvoEntHRWTemp
Heat Recovery Leaving Water Temperature
Keypad Menu Path:
This output network variable indicates the current temperature of the water leaving the heat recovery
section. (A23)
No Keypad Equivalent
Measurement
Temperature
BACnet
Variable Details
Object Type
Analog Input
LONWORKS
Variable Details
LONWORKS Name
nvoLvgHRWTemp
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
Object Identifier
Type Enumeration
0
HeatRecEntWaterTemp
Profile
Proprietary
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
Object Identifier
Type Enumeration
0
HeatRecLvgWaterTemp
Profile
Proprietary
Data Type
Valid Range
BACnet: Real
BACnet: -40°–244°F
LONWORKS:-40°–118°C
Instance
Property Name
5
Present Value
Object Name
SNVT Type
SNVT Index
temp_p
Data Type
Valid Range
BACnet: Real
BACnet: -40°–244°F
LONWORKS:-40°–118°C
Instance
Property Name
6
Present Value
Object Name
SNVT Type
SNVT Index
temp_p
70
d
d
P
I
eTaIled
aTa
oInT
Default Value
NA
Property Identifier
Property Enumeration
85
SNVT Size
105
two bytes
Default Value
NA
Property Identifier
Property Enumeration
85
SNVT Size
105
two bytes