Network Input Variables; Network Configuration Parameters - Daikin MicroTech II Installation And Maintenance Manual

Chiller unit controller
Table of Contents

Advertisement

Network Input Variables

Network Control Property
Keypad attributes available
as LONWORKS Variables for
network control of the unit
*Capacity Limit Setpoint (10)
*Chiller Enable (Input) (4)
Chiller Mode Setpoint
Compressor Select
*Cool Setpoint (9)
Heat Setpoint
Ice Setpoint
*Network Clear Alarm (12)
Pump Select
*Boldface denotes data points for typical minimum integration.

Network Configuration Parameters

Network Control Property
Keypad attributes available as LONWORKS
Variables for network control of the unit
Capacity Limit (LONWORKS Configuration)
Chiller Enable (LONWORKS Configuration)
Cool Setpoint (LONWORKS Configuration)
Default Values
Heat Setpoint (LONWORKS Configuration)
Chiller Location
Maximum Send Time
Minimum Send Time
*Chiller Mode (LONWORKS Configuration) (2)
Receive Heartbeat
*Boldface denotes data points for typical minimum integration.
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
SNVT
Variable Name
Page
Index
nviCapacityLim
25
81
nviChillerEnable
26
95
nviMode
31
108
nviCompSelect
43
nviCoolSetpt
58
105
nviHeatSetpt
71
105
nviIceSpt
72
105
nviClearAlarm
97
95
nviPumpSelect
85
95
Variable Name
nciCapacityLim
nciChillerEnable
nciCoolSetpt
nciDefaults
nciHeatSetpt
nciLocation
nciMaxSendTime
nciMinSendTime
nciMode
nciRcvHrtBt
Description
0 to 160%; Default=100%
0=Request Chiller OFF, 1=Request Chiller On; Default=OFF
1=HVAC_HEAT, 3=HVAC_COOL, 5=HVAC_PRE_COOL, 11=HVAC_ICE;
Default=Cool
8
See Variable Description
-12 .2– 48 .8°C; Default=7 .2°C
10–93°C; Default=35°C
-9.4– 1.7°C; Default=-3.9°C
0= Inactive,1=Clear Alarm; Default=0
0=Pump No. 1, 1=Pump No. 2; Default=0
SCPT
SCPT_Reference
Index
24
SCPT_limitChlrCap
27
SCPT_pwrUpState
58
SCPT_CoolSetpoint
59
SCPT_maxSendTime
71
SCPT_HeatSetpoint
29
SCPT_location
76
SCPT_maxSendTime
77
SCPT_minSendTime
29
SCPT_HVACmode
86
SCPT_maxRcvTime
20
C
d
omPrehensIve
aTa
Description
81
0% to 160%.
0=Request Chiller OFF, 1=Request
73
Chiller Auto (run)
75
-40°C to 93°C
0=Use Default Values, 1=Use
71
Manufacturer-Specified Values
78
-40–93°C
Any NUL terminated ASCII string up to
17
31 bytes.
52
0–6553.4 sec
52
0–6553.4 sec
1=HVAC_HEAT, 3=HVAC_COOL,
74
11=HVAC_ICE
49
0.0–6553.4 sec (0.1 sec)
www.DaikinApplied.com