Compressor Starts - Daikin MicroTech II Installation And Maintenance Manual

Chiller unit controller
Table of Contents

Advertisement

Compressor Starts

Keypad Menu Path:
Menu
\View
\Compressor
Measurement
Event Count
BACnet
Compressor Select
This output network variable indicates the number of times the compressor motor of the compressor selected with
Select on page 43
has started. (I45)
Object Type
Analog Input
Compressor #2
This variable indicates the number of times the compressor 2 motor has started. (I106)
Object Type
Analog Input
Compressor #3
This variable indicates the number of times the compressor 3 motor has started. (I109)
Object Type
Analog Input
Compressor #4
This variable indicates the number of times the compressor 4 motor has started. (I112)
Object Type
Analog Input
LONWORKS
Variable Details
This output network variable indicates the number of times the compressor motor of the compressor selected with
Select on page
43. (I45)
LONWORKS Name
nvoCompStarts
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Units
NA
LONWORKS: Fixed Point
Scalar - unsigned long
Object Identifier
Type Enumeration
0
Object Identifier
Type Enumeration
0
Object Identifier
Type Enumeration
0
Object Identifier
Type Enumeration
0
Profile
Proprietary
Data Type
Valid Range
BACnet: Real
Instance
Property Name
25
Present Value
Object Name
CompStarts
Instance
Property Name
92
Present Value
Object Name
Comp2Starts
Instance
Property Name
100
Present Value
Object Name
Comp3Starts
Instance
Property Name
108
Present Value
Object Name
Comp4Starts
SNVT Type
SNVT Index
count
44
d
d
P
eTaIled
aTa
oInT
Default Value
0–65,535
Compressor
Property Identifier
Property Enumeration
Property Identifier
Property Enumeration
Property Identifier
Property Enumeration
Property Identifier
Property Enumeration
Compressor
SNVT Size
8
two bytes
www.DaikinApplied.com
I
nformaTIon
NA
85
85
85
85