Daikin MicroTech II Installation And Maintenance Manual page 92

Chiller unit controller
Table of Contents

Advertisement

Alarm
Class Description
12
P
INHIBIT LOAD - Condenser Pressure High #2
13
P
INHIBIT LOAD - Condenser Pressure High #3
15
P
UNLOAD - Condenser Pressure High
16
P
UNLOAD - Condenser Pressure High #1
17
P
UNLOAD - Condenser Pressure High #2
18
P
UNLOAD - Condenser Pressure High #3
20
P
CONDENSER PUMP ON - Condenser Water Freeze Protection #1
21
P
CONDENSER PUMP ON - Condenser Water Freeze Protection #2
24
P
PUMP #2 START ATTEMPTED - Condenser Pump #1 Failure
25
P
PUMP #1 START ATTEMPTED - Condenser Pump #2 Failure
26
P
LOAD - Discharge Temperature High #1
27
P
LOAD - Discharge Temperature High #2
30
P
NO EWT RESET - Entering Evaporator Temperature Sensor Failure
31
P
INHIBIT LOAD - Evaporator Pressure Low
32
P
INHIBIT LOAD - Evaporator Pressure Low #1
33
P
INHIBIT LOAD - Evaporator Pressure Low #2
34
P
INHIBIT LOAD - Evaporator Pressure Low #3
36
P
UNLOAD - Evaporator Pressure Low
37
P
UNLOAD - Evaporator Pressure Low #1
38
P
UNLOAD - Evaporator Pressure Low #2
39
P
UNLOAD - Evaporator Pressure Low #3
41
P
UNLOAD - Compressor Motor Current High #1
42
P
UNLOAD - Compressor Motor Current High #2
43
P
UNLOAD - Compressor Motor Current High #3
EVAPORATOR PUMP ON - Evaporator Water Freeze Protection
45
P
Comp #1
EVAPORATOR PUMP ON - Evaporator Water Freeze Protection
46
P
Comp #2
49
P
PUMP #2 START ATTEMPTED - Evaporator Pump #1 Failure
50
P
PUMP #1 START ATTEMPTED - Evaporator Pump #2 Failure
COMPRESSOR SHUTDOWN - Outside Air Temperature Sensor
52
F
Fault
53
F
COMPRESSOR SHUTDOWN - Current Overload Trip #1
54
F
COMPRESSOR SHUTDOWN – Current Overload Trip #2
55
F
COMPRESSOR SHUTDOWN – Current Overload Trip #3
57
F
COMPRESSOR SHUTDOWN – Motor Current Imbalance #1
58
F
COMPRESSOR SHUTDOWN – Motor Current Imbalance #2
61
F
COMPRESSOR SHUTDOWN – Low Motor Current #1
62
F
COMPRESSOR SHUTDOWN – Low Motor Current #2
65
F
UNIT SHUTDOWN - Motor Protector Trip
66
F
COMPRESSOR SHUTDOWN - Motor Protector Trip #1
67
F
COMPRESSOR SHUTDOWN - Motor Protector Trip #2
68
F
COMPRESSOR SHUTDOWN - Motor Temperature High #1
69
F
COMPRESSOR SHUTDOWN - Motor Temperature High #2
70
F
COMPRESSOR SHUTDOWN - Motor Temperature High #3
72
F
COMPRESSOR SHUTDOWN - Phase Loss #1
73
F
COMPRESSOR SHUTDOWN - Phase Loss #2
74
F
COMPRESSOR SHUTDOWN - Phase Loss #3
76
F
COMPRESSOR SHUTDOWN - Phase Reversal #1
77
F
COMPRESSOR SHUTDOWN - Phase Reversal #2
78
F
COMPRESSOR SHUTDOWN - Phase Reversal #3
80
F
COMPRESSOR SHUTDOWN - Overvoltage #1
81
F
COMPRESSOR SHUTDOWN - Overvoltage #2
1-AGS 'C' Vintage Only (two circuits only)
2-AGS 'B' Vintage Only (up to three circuits)
3-ACZ Dual Circuit Only
4-ACZ Single Circuit Only
5-AGZ Dual Circuit Only
6-AGZ Single Circuit Only
7-Solid State Starter Option required. Not available on WMC.
8-WMC Only.
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
WSC, WDC,
WPV, HSC,
Event Values
HDC, TSC,
WMC, WCC
1,2,9,10
1,2,9,10
1,2,9,10
1,2,3,4,9,10
1,2,3,4,9,10
1,2,9,10
1,2,3,4,9
X
1,2,3,4,9
X
X
1,2,3,4,9
X
1,2,3,4,9
1,2,3,4,9
X
1,2,3,4,9
X
1,2,3,4,9
X
1,2,3,4,9,10
1,2,3,4,9,10
X
1,2,3,4,9,10
X
1,2,9,10
1,2,3,4,9,10
1,2,3,4,9,10
X
1,2,3,4,9,10
X
1,2,9,10
1,2,3,4,9,10
X
X
1,2,3,4,9,10
1,2,9,10
1,2,3,4,9
X
1,2,3,4,9
X
1,2,3,4,9
X
1,2,3,4,9
X
1,2,3,4,9,10
1,2,3,4,9,10
X
1,2,3,4,9,10
X
1,2,9,10
X
1,2,9,10
1,2,9,10
X
1,2,9,10
X
1,2,9,10
X
1,2,3,4,9,10
1,2,3,4,9,10
1,2,3,4,9,10
1,2,3,4,9,10
X
1,2,3,4,9,10
X
1,2,9,10
1,2,3,4,9,10
X
7
1,2,3,4,9,10
X
7
1,2,9,10
X
1,2,3,4,9,10
7
X
1,2,3,4,9,10
7
1,2,9,10
1,2,3,4,9,10
X
7
1,2,3,4,9,10
X
7
92
C
a
-baC
learIng
larms
AGZ
ACZ
WGZ, TGZ
AGS
X
X
X
X
5
3
X
2
X
X
X
5
X
3
X
X
X
5
X
3
X
X
X
2
X
X
X
X
6
4
X
X
X
X
5
3
X
X
X
X
5
3
X
2
X
6
X
4
X
5
X
3
X
X
X
5
X
3
X
X
X
2
X
2
X
X
X
X
X
X
X
2
X
X
X
X
6
4
X
X
X
5
3
X
X
X
5
3
X
X
X
2
X
5
X
3
X
X
1
X
5
X
3
X
X
1
X
2
X
1
X
1
X
2
X
1
X
1