Ice Setpoint
Keypad Menu Path:
The Ice Setpoint data point determines the temperature of the Leaving Chilled Water. LONWORKS
network variables set the operating Temperature. The BACnet property is a commandable property of a
Menu
Analog Output object. Refer to the appropriate Operation Manual for suitable variable values. (A30)
\Set
\Unit SPs (3)
Measurement
Temperature
BACnet
This commandable property sets the temperature of the Leaving Chilled Water. This level may be adjusted via an operator
workstation or other network device. When this property is read, it indicates the current value of the temperature of the Leaving
Chilled Water.
Variable Details
Object Type
Analog Output
Default Value (Relinquish_Default) 25°F
LONWORKS
Input (nvi)
This input network variable provides the Ice setpoint of the Leaving Chilled Water when the chiller is operating in the Ice Mode.
Variable Details
LONWORKS Name
nviIceSpt
Default Value -3.9°C
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
Object Identifier
Type Enumeration
1
NetworkIceTempSetpoint
Profile
Chiller
Data Type
Valid Range
BACnet: Real
Dependent on Chiller Mode
Instance
Property Name
30
Present Value
Object Name
SNVT Type
SNVT Index
temp_p
72
d
d
P
eTaIled
aTa
oInT
Default Value
See below
and Model
Property Identifier
Property Enumeration
SNVT Size
105
two bytes
www.DaikinApplied.com