Compressor Suction Line Temperature
Keypad Menu Path:
Menu
\View
\Unit
\Refrigerant (2)
Measurement
Temperature
BACnet
Compressor Select
This output network variable indicates the current suction line refrigerant temperature. There is a separate output for each
compressor. See
Compressor Select on page
Object Type
Analog Input
Compressor #2
This variable indicates the current suction line refrigerant temperature for compressor 2. Not available on all chiller models. (A88)
Object Type
Analog Input
LONWORKS
Variable Details
This output network variable indicates the current suction line refrigerant temperature. There is a separate output for each
compressor. See
Compressor Select on page
LONWORKS Name
nvoSuctionTemp
www.DaikinApplied.com
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
43. (A15)
Object Identifier
Type Enumeration
0
Object Identifier
Type Enumeration
0
Comp2SuctTemp
43. (A15)
Profile
Proprietary
Data Type
Valid Range
BACnet: Real
BACnet: -40°–244°F
LONWORKS: -40°–118°C
Instance
Property Name
15
Present Value
Object Name
SuctionTemp
Instance
Property Name
69
Present Value
Object Name
SNVT Type
SNVT Index
temp_p
47
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
I
eTaIled
aTa
oInT
Default Value
NA
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85
SNVT Size
105
two bytes
nformaTIon