Chiller Location

Keypad Menu Path:
This configuration network parameter provides a description of the location.
No Keypad Equivalent
Measurement
NA
LONWORKS
Variable Details
LONWORKS Name
Profile
nciLocation
Chiller
Structure
typedef struct {
unsigned char ascii[31];
} SNVT_str_asc;

Chiller Mode

Keypad Menu Path:
This LONWORKS configuration network parameter establishes the default operating mode of the chiller,
unless the configuration parameter nciDefaults = 1 (See
No Keypad Equivalent
1, the default values are the values specified during manufacturing.
• Heat Mode
• Cool Mode (default)
• Ice Mode
Measurement
HVAC Mode
LONWORKS
Default Value
3 = HVAC_COOL
The chiller object uses the configuration value of nciMode on power-up or loss of communication unless the configuration
parameter nciDefaults =1 (See
Variable Details
LONWORKS Name
Profile
nciMode
Chiller
www.DaikinApplied.com
Units
NA
SNVT Type
str_asc
Units
NA
Default Values on page
59).
SNVT Type
hvac_mode
Data Type
Any NUL terminated ASCII
Structure
string up to 31 bytes.
SNVT Index
SNVT Size
36
31 bytes max
Default Values on page
Data Type
Unsigned Integer
SNVT Index
SNVT Size
108
one byte
29
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
eTaIled
aTa
oInT
Valid Range
Default Value
ASCII string of zeros + NUL
SCPT_Reference
SCPT_location
59). If nciDefaults =
Valid Range
Default Value
Enumerated
See Below
SCPT Reference
SCPT_HVACmode
I
nformaTIon
SCPT Index
17
SCPT Index
74