Network Control Property
Keypad attributes available as BACnet
Standard Objects for network control
of the unit
Evaporator Pump Run Hours
Pump Select
Pump #2
Evaporator Refrigerant Pressure
Compressor Select
Compressor #2
Evaporator Saturated Refrigerant
Temperature
Compressor Select
Compressor #2
Evaporator Water Flow Rate
Evaporator Water Pump Status
Heat Recovery Entering Water
Temperature
Heat Recovery Leaving Water
Temperature
Heat Setpoint
Ice Setpoint
IGV Percentage Open
Compressor #1
Compressor #2
Inverter Temperature
Compressor #1
Compressor #2
Liquid Line Refrigerant Pressure
Liquid Line Refrigerant Temperature
Compressor Select
Compressor #2
Maximum RPM
Compressor #1
Compressor #2
Minimum RPM
Compressor #1
Compressor #2
Motor Cavity Temperature
Compressor #1
Compressor #2
Oil Feed Pressure
Compressor Select
Compressor #2
Oil Feed Temperature
Compressor Select
Compressor #2
Oil Sump Pressure
Compressor Select
Compressor #2
Oil Sump Temperature
Compressor Select
Compressor #2
Outdoor Air Temperature
*Boldface denotes data points for typical minimum integration.
www.DaikinApplied.com
Description
Hours reported at 1/10th the actual hours.
65
R
AI
27
0–65,535
AI
89
0–65,535.
66
R
AI
13
-3276.8–3276.7
AI
71
-3276.8–3276.7
AI
14
-40°–244°F
67
R
AI
70
-40°–244°F
68
R
AI
49
Flow Rate in GPM Centrifugals Only
69
R
BI
36
0=No Flow, 1=Flow
70
R
AI
5
-40°–244°F
70
R
AI
6
-40°–244°F
71
W
AO
31
50–150°F, Default=95°F
72
W
AO
30
15– 35°F, Default=25°F
73
R
AI
58
0–110%
AI
62
73
R
AI
66
AI
87
74
R
AI
12
-22592–22591 psi
75
R
AI
11
-40°–244°F
AI
85
-40°–244°F
76
R
AI
55
0–32678
AI
59
77
R
AI
57
0–32678
AI
61
78
R
AI
65
AI
86
79
R
AI
19
-22592–22591 psi
AI
81
-22592–22591 psi
80
R
AI
21
-40°–244°F
AI
83
-40°–244°F
81
R
AI
20
-22592–22591 psi
AI
82
-22592–22591 psi
82
R
AI
22
-40°–244°F
AI
84
-40°–244°F
83
R
AI
10
-40°–244°F
17
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
C
d
P
omPrehensIve
aTa
oInT
T
ables