Motor Cavity Temperature
Keypad Menu Path:
This output data point indicates the current temperature of the compressor's motor stator cavity. (A85 &
A105)
No Keypad Equivalent
Measurement
Temperature
BACnet
Compressor #1
Object Type
Analog Input
Compressor #2
Object Type
Analog Input
LONWORKS
No LONWORKS equivalent.
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Units
BACnet: °F
Object Identifier
Type Enumeration
0
Comp1MotorCavityTmp
Object Identifier
Type Enumeration
0
Comp2MotorCavityTmp
Data Type
Valid Range
BACnet: Real
BACnet: -4°–212°F
Instance
Property Name
65
Present Value
Object Name
Instance
Property Name
86
Present Value
Object Name
78