Actual RPM
Keypad Menu Path:
This variable indicates the actual speed of the compressor. (I118 & I122)
No Keypad Equivalent
Measurement
Revolutions per Minute
BACnet
Compressor #1
Object Type
Analog Input
Compressor #2
Object Type
Analog Input
LONWORKS
No LONWORKS equivalent.
Capacity Limit
Keypad Menu Path:
Capacity Limit is a measure of the ratio of operating capacity to full capacity expressed in percent. This
LONWORKS variable sets a default value for the capacity limit of the chiller, unless the configuration
No Keypad Equivalent
property, nciDefaults = 1 (See
the values specified during manufacturing. The capacity limit value is not the nominal capacity limit of
the Chiller. Refer to the appropriate Operating Manual for suitable variable values.
Measurement
Percent of maximum capacity
LONWORKS
Default Value
100% The chiller object uses the configuration value of nciCapacityLim on power-up or loss of communication unless
the configuration parameter nciDefaults = (see
Variable Details
LONWORKS Name
Profile
nciCapacityLim
Chiller
(configuration)
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Units
BACnet: RPM
Object Identifier
Type Enumeration
0
Comp1ActualRPM
Object Identifier
Type Enumeration
0
Comp2ActualRPM
Default Values on page
Units
LONWORKS: Fixed-Point
NA
Scalar signed long
SNVT Type
Data Type
Valid Range
BACnet: Real
BACnet: 0–-32678
Instance
Property Name
56
Present Value
Object Name
Instance
Property Name
60
Present Value
Object Name
59). If nciDefaults = 1, the default values are
Data Type
Valid Range
0% to 160%.
Default Values on page
SNVT Index
SNVT Size
81
two bytes
24
d
d
P
I
eTaIled
aTa
oInT
Default Value
NA
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85
Default Value
See Below
59).
SCPT_Reference
SCPT Index
SCPTlimitChlrCap
www.DaikinApplied.com
nformaTIon
81