IGV Percentage Open

Keypad Menu Path:
This output network variable indicates current percent of vanes open for each compressor (0%=closed,
110%=full capacity-open) (I120 & I124)
No Keypad Equivalent
Measurement
Percent
BACnet
Compressor #1
Object Type
Analog Input
Compressor #2
Object Type
Analog Input
LONWORKS
No LONWORKS equivalent.

Inverter Temperature

Keypad Menu Path:
This output network variable the current drive temperature. There is one variable for each compressor.
(A86 & A106)
No Keypad Equivalent
Measurement
Temperature
BACnet
Compressor #1
Object Type
Analog Input
Compressor #2
Object Type
Analog Input
LONWORKS
No LONWORKS equivalent.
www.DaikinApplied.com
Units
BACnet: %
Object Identifier
Type Enumeration
0
Comp1IGVPercentOpen
Object Identifier
Type Enumeration
0
Comp2IGVPercentOpen
Units
BACnet: °F
Object Identifier
Type Enumeration
0
Comp1InverterTmp
Object Identifier
Type Enumeration
0
Comp2InverterTmp
Data Type
Valid Range
BACnet: Real
BACnet: 0–110
Instance
Property Name
58
Present Value
Object Name
Instance
Property Name
62
Present Value
Object Name
Data Type
Valid Range
BACnet: Real
BACnet: 32.0–212.0°F
Instance
Property Name
66
Present Value
Object Name
Instance
Property Name
87
Present Value
Object Name
73
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
I
eTaIled
aTa
oInT
nformaTIon
Default Value
NA
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85
Default Value
NA
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85