Unit Status; Ice Mode Start Delay; Evaporator Pump Control - Daikin MICROTECH III Operating Manual

Water-cooled screw chiller
Hide thumbs Also See for MICROTECH III:
Table of Contents

Advertisement

7.6

Unit Status

The displayed unit status is determined by the conditions in the following table:
Enum
0
1
Off:Ice Mode Timer
2
3
Off:All Cir Disabled
4
Off:Unit Alarm
5
Off:Keypad Disable
6
Off:Remote Switch
7
Off:BAS Disable
8
Off:Unit Switch
9
Off:Test Mode
10
Auto:Noise Reduction
11
Auto:Wait for load
12
Auto:Evap Recirc
13
Auto:Wait for flow
14
Auto:Pumpdown
15
Auto:Max Pulldown
16
Auto:Unit Cap Limit
17
Auto:Current Limit
18
Off:Config Changed, Reboot
19
Off:Set Mfg Location
7.7

Ice Mode Start Delay

An adjustable start-to-start ice delay timer will limit the frequency with which the chiller may start in Ice mode. The timer
starts when the first compressor starts while the unit is in ice mode. While this timer is active, the chiller cannot restart in
Ice mode. The time delay is user adjustable.
The ice delay timer may be manually cleared to force a restart in ice mode. A set point specific ally for clearing the ice mode
delay is available. In addition, cycling the power to the controller will clear the ice delay timer.
7.8

Evaporator Pump Control

Three evaporator pump control states for control of the evaporator pumps:
Off - No pump on.
Start – Pump is on, water loop is being recirculated.
Run – Pump is on, water loop has been recirculated.
The control state is Off when all of the following are true:
Unit state is Off
LWT is higher than the Evap Freeze set point or LWT sensor fault is active
EWT is higher than the Evap Freeze set point or EWT sensor fault is active
The control state is Start when any of the following are true:
The unit state is auto
LWT is less than the Evap Freeze set point minus 0.6 °C and LWT sensor fault isn't active
EWT is less than the Evap Freeze set point minus 0.6 °C and EWT sensor fault isn't active
The control state is Run when the flow switch input has been closed for a time greater than the Evaporator Recirculate set
point.
19/77
Status
Auto
-
Unit State = Off, Control Source = Network, and BAS Enable = false
Unit State = Auto, no circuits running, and LWT is less than the active
Unit State = Auto, Evaporator State = Start, and Flow Switch is open
Operation Manual
Unit State = Auto
Unit State = Off, Unit Mode = Ice, and Ice Delay = Active
Unit State = Off and all compressors unavailable
Unit State = Off and Unit Alarm active
Unit State = Off and Unit Enable Set Point = Disable
Unit State = Off and Remote Switch is open
Unit State = Off and Unit Switch = Disable
Unit State = Off and Unit Mode = Test
Unit State = Auto and Noise Reduction is active
set point + startup delta
Unit State = Auto and Evaporator State = Start
Unit State = Pumpdown
Unit State = Auto, max pulldown rate has been met or exceeded
Unit State = Auto, unit capacity limit has been met or exceeded
Unit State = Auto, unit current limit has been met or exceeded
Unit State = Off and Unit Enable Set Point = Disable
Unit State = Off and Unit Enable Set Point = Disable
Conditions
-
D–EOMWC00A07-16_02EN