Fault Alarms, Multi-state Input Object
This BACnet object indicates the index number of Fault
Alarms in the present value property and the text of the alarm
message in the state text property. If the present value is zero,
no alarm has occurred. See
Measurement
NA
Object Type
Multi-state Input
Measurement
NA
Object Type
Multi-state Input

Poll Singular

Alarm Digital Output
The Poll Singular method requires that one Binary Input object
in the BACnet Communication Module be polled for alarm
notification. This object indicates whether an alarm condition has
occurred. The operator interface displays the alarm text. (D3)
Measurement
NA
Object Type
Binary Input
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Table 4 on page
91.
Units
NA
Object Identifier
Type Enumeration
13
Units
NA
Object Identifier
Type Enumeration
13
Units
NA
Object Identifier
Type Enumeration
3
Data Type
Integer
Instance
901
Object Name
MSIFaultAlarm
Data Type
Character String
Instance
901
Object Name
MSIFaultAlarm
Data Type
Integer
Instance
40
Object Name
AlarmDigitalOutput
Property Values
0 = No Alarm
1 = Alarm
90
a
Valid Range
Default Value
Enumerated
Property Identifier
Property Name
Property Enumeration
Present Value
Valid Range
Default Value
NA
Property Identifier
Property Name
Property Enumeration
State Text
Valid Range
Default Value
Enumerated
Property Identifier
Property Name
Property Enumeration
Present Value
www.DaikinApplied.com
-baC
larms
neT
NA
85
NA
110
NA
85