Evaporator Water Pump Status
Keypad Menu Path:
This output network variable indicates whether the selected pump has been commanded ON or OFF.
See
No Keypad Equivalent
Measurement
Flow State
BACnet
Variable Details
Object Type
Binary Input
LONWORKS
Variable Details
LONWORKS Name
nvoChWPump
Structure
typedef struct {
unsigned
value;
signed
state;
} SNVT_switch;
Valid Range
Value Field
unused
State Field
0
Pump Commanded Off
1
Pump Commanded On
www.DaikinApplied.com
Pump Select on page
85. (D29)
Units
BACnet: Enumerated
NA
LONWORKS: Structure
Object Identifier
Type Enumeration
3
0 = Commanded Off(Inactive)
1 = Commanded On(Active)
Profile
Proprietary
Data Type
Instance
Property Name
36
Object Name
EvapPumpState
Property Values
SNVT Type
switch
69
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
eTaIled
aTa
oInT
Valid Range
Default Value
See Below
Property Identifier
Property Enumeration
Present Value
SNVT Index
SNVT Size
95
I
nformaTIon
NA
85
two bytes
Need help?
Do you have a question about the MicroTech II and is the answer not in the manual?
Questions and answers