Evaporator Entering Water Temperature - Daikin MicroTech II Installation And Maintenance Manual

Chiller unit controller
Table of Contents

Advertisement

Evaporator Entering Water Temperature

Keypad Menu Path:
This output attribute indicates the temperature of the evaporator entering water temperature. (A4)
Menu
\View
\Unit
\Water
Measurement
Temperature
BACnet
Variable Details
Object Type
Analog Input
LONWORKS
Variable Details
LONWORKS Name
nvoEntChwTemp
www.DaikinApplied.com
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
Object Identifier
Type Enumeration
0
EntEvapWaterTemp
Profile
Chiller
Data Type
Valid Range
BACnet: Real
BACnet: -40–245°F
LONWORKS: -40°–118°C
Instance
Property Name
1
Present Value
Object Name
SNVT Type
SNVT Index
temp_p
61
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
I
eTaIled
aTa
oInT
Default Value
NA
Property Identifier
Property Enumeration
85
SNVT Size
105
two bytes