Chiller Alarm Objects - Daikin MicroTech II Installation And Maintenance Manual

Chiller unit controller
Table of Contents

Advertisement

Network Control Property
Keypad attributes available as BACnet
Standard Objects for network control
of the unit
Power Factor
Compressor Select
Compressor #2
Compressor #3
Compressor #4
Compressor #5
Compressor #6
Pump Select
Run Enabled
*Boldface denotes data points for typical minimum integration.

Chiller Alarm Objects

Network Control Property
Keypad attributes available as BACnet Standard
Objects for network control of the unit
Warning Alarms, Analog Input Object (11)
Problem Alarms, Analog Input Object (11)
Fault Alarms, Analog Input Object (11)
Warning Alarms, Multi-state Input Object (11)
Problem Alarms, Multi-state Input Object (11)
Fault Alarms, Multi-state Input Object (11)
Alarm Digital Output (11)
BACnet Clear Alarm (12)
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Description
AI
53
AI
78
84
R
AI
97
-99 – +100
AI
105
AI
113
AI
119
85
W
MSO
47
1=Pump No. 1, 2=Pump No. 2; Default=1
86
R
BI
33
0=OFF, 1=Run Allowed
88
R
AI
88
R
AI
88
R
AI
89
R
MSI
89
R
MSI
90
R
MSI
90
R
BI
91
W
BV
Description
902
Alarm Index
900
Alarm Index
901
Alarm Index
902
Alarm Index and Alarm Text (30 characters max)
900
Alarm Index and Alarm Text (30 characters max)
901
Alarm Index and Alarm Text (30 characters max)
40
0-No Alarm, 1=Alarm
42
0= Normal, 1=Clear Alarm
18
C
d
P
omPrehensIve
aTa
oInT