Condenser Flow Switch Status - Daikin MicroTech II Installation And Maintenance Manual

Chiller unit controller
Table of Contents

Advertisement

Condenser Flow Switch Status

Keypad Menu Path:
This output network variable indicates the status of the water flow through the condenser. (D8)
No Keypad Equivalent
Measurement
Flow State
BACnet
Variable Details
Object Type
Binary Input
CondWaterFlowStatus
LONWORKS
Variable Details
LONWORKS Name
nvoCndWFlow
Structure
typedef struct {
unsigned value;
signed
state;
} SNVT_switch;
Valid Range
Value Field unused
State Field
0
No Flow
1
Flow
www.DaikinApplied.com
Units
BACnet: Enumerated
NA
LONWORKS: Structure
Object Identifier
Type Enumeration
3
Property Values
0 = No Flow(Inactive)
1 = Flow(Active)
Profile
Proprietary
Data Type
Valid Range
Instance
Property Name
35
Present Value
Object Name
SNVT Type
SNVT Index
switch
51
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
eTaIled
aTa
oInT
Default Value
See Below
Property Identifier
Property Enumeration
SNVT Size
95
two bytes
I
nformaTIon
NA
85