Capacity Limit Output

Keypad Menu Path:
This output variable is a measure of the ratio of operating capacity to full capacity expressed in percent.
This output variable indicates the current value of the Capacity Limit. (A42)
No Keypad Equivalent
Measurement
Percent of maximum capacity
BACnet
Variable Details
Object Type
Analog Input
LONWORKS
Variable Details
LONWORKS Name
Profile
nvoCapacityLim
Chiller
(output)

Capacity Limit Setpoint

Keypad Menu Path:
Capacity Limit is a measure of the ratio of operating capacity to full capacity expressed in percent. This
level may be adjusted via an operator workstation or other network device, but cannot be adjusted
No Keypad Equivalent
above a factory-specified limit. The input network variable sets the operating value (input). Refer to the
appropriate Operation Manual for suitable variable values. (A3)
Measurement
Percent of maximum capacity
BACnet
This read or read/write property sets the maximum capacity limit of the chiller. This level may be adjusted, but cannot be adjusted
above a factory-specified limit.
Variable Details
Object Type
Analog Output
Default Value (Relinquish_Default)
100%
LONWORKS
Input (nvi) The input network variable sets the maximum capacity level of the chiller. This level may be adjusted via an operator
workstation or other network device, but cannot be adjusted above a factory-specified limit.
Variable Details
LONWORKS Name
Profile
nviCapacityLim
Chiller
(input)
www.DaikinApplied.com
Units
NA
LONWORKS: Fixed-Point
Scalar signed long
Object Identifier
Type Enumeration
0
ActiveCapacityLimit
SNVT Type
lev_percent
Units
NA
LONWORKS: Fixed-Point
Scalar signed long
Object Identifier
Type Enumeration
1
NetworkCapacityLimitPct
SNVT Type
lev_percent
Data Type
Valid Range
BACnet: Real
0% to 160%.
Instance
Property Name
8
Present Value
Object Name
SNVT Index
SNVT Size
81
two bytes
Data Type
Valid Range
BACnet: Real
0% to 160%.
Instance
Property Name
32
Present Value
Object Name
SNVT Index
SNVT Size
81
two bytes
25
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
I
eTaIled
aTa
oInT
nformaTIon
Default Value
See Below
Property Identifier
Property Enumeration
85
SCPT_Reference
SCPT Index
NA
Default Value
See Below
Property Identifier
Property Enumeration
85
SCPT_Reference
SCPT Index
NA
NA
NA