Compressor #4
This output network variable indicates the compressor status of the compressor 42. (I111)
Object Type
Analog Input
Compressor #5
This output network variable indicates the compressor status of the compressor 5. (I114)
Object Type
Analog Input
Compressor #6
This output network variable indicates the compressor status of the compressor 6. (I115)
Object Type
Analog Input
LONWORKS
No LONWORKS equivalent.
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Object Identifier
Type Enumeration
0
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Object Identifier
Type Enumeration
0
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Object Identifier
Type Enumeration
0
0=Off
1=Start Oil Pump
2=Interlock/Prelube
3=Run
4=Shutdown
Instance
Property Name
107
Present Value
Object Name
Comp4Status
Instance
Property Name
115
Present Value
Object Name
Comp5Status
Instance
Property Name
121
Present Value
Object Name
Comp6Status
46
d
d
P
I
eTaIled
aTa
oInT
nformaTIon
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85
Property Identifier
Property Enumeration
85
www.DaikinApplied.com