Evaporator Pump Run Hours
Keypad Menu Path:
NOTE: Value returned must be multiplied by 10 to give run hours.
No Keypad Equivalent
Measurement
Event Count
BACnet
Pump Select
This output network variable indicates the number of hours (x10) that the selected evaporator pump has been turned on. There is a
separate output for each pump. See
Object Type
Analog Input
Pump #2
This variable indicates the number of hours (x10) for pump 2. Not available on all chiller models. (I105)
Object Type
Analog Input
LONWORKS
Variable Details
This output network variable indicates the number of hours (x10) that the selected evaporator pump has been turned on. See
Pump Select on page
85. (I47)
LONWORKS Name
nvoEvapPumpHrs
www.DaikinApplied.com
Units
NA
LONWORKS: Fixed-Point
Pump Select on page
85. (I47)
Object Identifier
Type Enumeration
0
EvapPumpOperHours
Object Identifier
Type Enumeration
0
Profile
Proprietary
Data Type
Valid Range
BACnet: Real
unsigned long
Instance
Property Name
27
Present Value
Object Name
Instance
Property Name
89
Present Value
Object Name
EvapPmp2Hrs
SNVT Type
SNVT Index
count
65
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
eTaIled
aTa
oInT
Default Value
0–65,535
Property Identifier
Property Enumeration
Property Identifier
Property Enumeration
SNVT Size
8
two bytes
I
nformaTIon
NA
85
85