Evaporator Water Flow Rate
Keypad Menu Path:
This output network variable indicates the current evaporator water flow rate. (A18)
No Keypad Equivalent
Measurement
Flow Volume
BACnet
Variable Details
Object Type
Analog Input
LONWORKS
Variable Details
LONWORKS Name
nvoEvapFlowRate
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
Units
BACnet: GPM
LONWORKS: Fixed Point
LONWORKS: L/S
Scalar unsigned long
Object Identifier
Type Enumeration
0
EvapWaterFlowRate
Profile
Proprietary
Data Type
Valid Range
BACnet: Real
BACnet: 0–65,534
LONWORKS: 0–65,534
Instance
Property Name
49
Present Value
Object Name
SNVT Type
SNVT Index
flow
68
d
d
P
I
eTaIled
aTa
oInT
Default Value
NA
Property Identifier
Property Enumeration
85
SNVT Size
15
two bytes
www.DaikinApplied.com
nformaTIon
Need help?
Do you have a question about the MicroTech II and is the answer not in the manual?