Liquid Line Refrigerant Temperature
Keypad Menu Path:
Menu
\View
\Unit \Refrg (2)
Liquid Line=
Measurement
Temperature
BACnet
Compressor Select
This output network variable indicates the current liquid line refrigerant temperature. There is a separate output for each
compressor/circuit. See
Compressor Select on page
Object Type
Analog Input
Compressor #2
This variable indicates the current liquid line refrigerant temperature for compressor 2. Not available on all chiller models. (A104)
Object Type
Analog Input
LONWORKS
Variable Details
This output network variable indicates the current liquid line refrigerant temperature. There is a separate output for each
compressor/circuit. See
Compressor Select on page
LONWORKS Name
nvoLiquLineTemp
www.DaikinApplied.com
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
43. (A36)
Object Identifier
Type Enumeration
0
Object Identifier
Type Enumeration
0
Comp2LiqLineTemp
43. (A36)
Profile
Proprietary
Data Type
BACnet: Real
BACnet: -40°–244°F
LONWORKS: -40°–118°C
Instance
Property Name
11
Present Value
Object Name
LiquidLineTemp
Instance
Property Name
85
Present Value
Object Name
SNVT Type
temp_p
75
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
eTaIled
aTa
oInT
Valid Range
Default Value
Property Identifier
Property Enumeration
Property Identifier
Property Enumeration
SNVT Index
SNVT Size
105
I
nformaTIon
NA
85
85
two bytes