Compressor #6
This variable indicates the current compressor amperes of compressor 6. (A124)
Object Type
Analog Input
LONWORKS
Variable Details
This output network variable indicates the current compressor amperes of the compressor selected with
page
43. (A26)
LONWORKS Name
nvoCurrent
Compressor Discharge Temperature
Keypad Menu Path:
Menu
\View
\Comp (5)
Measurement
Temperature
BACnet
Compressor Select
This output network variable indicates the current compressor refrigerant temperature of the compressor selected with
Select on page
43. (A19)
Object Type
Analog Input
Compressor #2
This variable indicates the current compressor refrigerant temperature of compressor 2. Not available on all chiller models. (A91)
Object Type
Analog Input
LONWORKS
Variable Details
This output network variable indicates the current compressor refrigerant temperature of the compressor selected with
Select on page
43. (A19)
LONWORKS Name
nvoCompDisTemp
www.DaikinApplied.com
Object Identifier
Type Enumeration
0
Profile
Proprietary
Units
BACnet: °F
LONWORKS: Fixed Point
LONWORKS: °C
Scalar signed long
Object Identifier
Type Enumeration
0
Object Identifier
Type Enumeration
0
Comp2DischargeTmp
Profile
Proprietary
Instance
Property Name
117
Present Value
Object Name
Comp6Current
SNVT Type
amp
Data Type
BACnet: Real
BACnet: -460°–621°F
LONWORKS:
-273.17°–327.66°C
Instance
Property Name
18
Present Value
Object Name
DischargeTemp
Instance
Property Name
Present Value
Object Name
SNVT Type
temp_p
37
ED 15062-7 • MICROTECH II CHILLER CONTROLLER
d
d
P
eTaIled
aTa
oInT
Property Identifier
Property Enumeration
Compressor Select on
SNVT Index
SNVT Size
1
Valid Range
Default Value
Property Identifier
Property Enumeration
Property Identifier
Property Enumeration
SNVT Index
SNVT Size
105
I
nformaTIon
85
two bytes
NA
Compressor
85
85
Compressor
two bytes