Temperature Menu; Flow Status Menu; Rf/Ef Control Menu; Saf Spd Control Menu - Daikin MicroTech III DPS Installation And Maintenance Manual

Iii unit controller for rebel refrigeration only controls
Table of Contents

Advertisement

Temperature Menu

Menus in the Temperatures menu contain unit temperature status information .
Table 4: Temperature Menu
Item Display Name
OA Temp=
DRT1=
DRT3=
SRT=
DFT=
IRT=
ORT=
INVCompTemp=
OA Temp is a status only item which displays the current
temperature reading from the unit mounted outdoor air
temperature sensor .
DRT1 is a status only item which displays the current inverter
compressor discharge refrigerant line temperature sensor
reading .
DRT3 is a status only item which displays the current fixed
compressor (Comp 3) discharge refrigerant line temperature
sensor reading .
SRT is a status only item which displays the current suction
refrigerant line temperature sensor reading .

Flow Status Menu

Table 5: Flow Status Menu
Item Display
Default Setting
Name
Supply Fan=
Ret/Exh Fan=
Supply Fan is a status only item that indicates the current S/S
state of the supply fan .
Ret/Exh Fan is a status only item that indicates the current S/S
state of the exhaust or return fan .

RF/EF Control Menu

Table 6: Return/Exhaust Fan Speed Menu
Item Display
Default Setting
Name
RF/EF Cap=
RF/EF Spd Cmd=
RF/EF Cap is a status only item which indicates the current
exhaust fan capacity .
RF/EF Spd Cmd is an adjustable input to command the return/
exhaust fan speed .
OM 1263 • MICROTECH UNIT CONTROLLER
Default Setting
Range
Password Level
Off
6
On
Off
6
On
Range
Password Level
0 – 100%
6
0 – 100%
6
Range
-50 .0 – 200 .0°F
-50 .0 – 392 .0°F
-50 .0 – 392 .0°F
-50 .0 – 200 .0°F
-50 .0 – 200 .0°F
-50 .0 – 150 .0°F
-50 .0 – 150 .0°F
-50 .0 – 392 .0°F
DFT (Heat Pump only) is a status only item which displays the
current defrost temperature sensor reading .
IRT (Heat Pump only) is a status only item which displays the
current indoor refrigerant temperature sensor reading .
ORT (Heat Pump only) is a status only item which displays the
current outdoor refrigerant temperature sensor reading .
INVCompTemp (15 ton unit size only) is a status only
item which displays the current inverter compressor body
temperature sensor reading .

SAF Spd Control Menu

Table 7: Supply Fan Speed Menu
Item Display
Default Setting
Name
SAF Speed=
SAF Spd Cmd=
SAF Speed is a status only item that indicates the current
supply fan speed .
Speed Cmd is a status only item that indicates the current
supply fan commanded speed .
20
View/Set Menu
Password Level
6
6
6
6
6
6
6
2
Range
Password Level
0 – 100%
6
0 – 100%
6
www .DaikinApplied .com