Variable Compressor Set-Up - Daikin MicroTech III Operation Manuals

For commercial rooftop, applied rooftop and self-contained systems
Hide thumbs Also See for MicroTech III:
Table of Contents

Advertisement

Variable Compressor Set-up

Table 25: Variable Compresor Setup Menu
Item Display Name
Compressor Status
Var Cmp Status=
Var Spd Cmd=
Comp 1=
Comp 3=
Comp 5=
Refrig Circuit Status
PTD1=
PTD2=
VCmpDischSH=
C1DschSatTmp=
C2DschSatTmp=
DRT1=
DRT2=
Cond Sol 1=
Cond Sol 2=
Compressor Setup
Var Cmp Period=
Var Cmp Gain=
Var Cmp PAT=
VarCmp MaxChg=
OilBoost=
LowOilTime=
OilBoostTime=
LowTcOAT=
OM 920-6 • MICROTECH UNIT CONTROLLER
Default Setting
OFF
OFF
20s
1
40s
10%
OFF
10m
15m
80°F
42
Range
OFF
ON
0–100%
OFF
ON
OFF
ON
OFF
ON
0–5000kPa
0–5000kPa
-100 .0–100 .0°F
-50 .0–212 .0°F
-50 .0–212 .0°F
-50 .0–392 .0°F
-50 .0–392 .0°F
OFF
ON
OFF
ON
1–300s
0 .0–100 .0
0–999s
0–50%
OFF
ON
1–30m
1–15m
50–122°F
M
d
enu
esCrIpTIons
Password Level
4
4
4
4
4
4
4
4
4
4
6
6
4
4
4
4
4
4
2
2
2
2
www .DaikinApplied .com

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MicroTech III and is the answer not in the manual?

Questions and answers

Table of Contents

Save PDF