Inverter Compressor Set-Up
(See page 51 — 56 for more information)
Table 13: Inverter Compressor Set Up Menu
Item Display
Default Setting
Name
Compressor Status
Clg State=
—
Htg State=
—
INV Cmp Spd=
—
INV Spd Cmd=
—
VCmpOilStatus=
—
Comp 3=
—
Fault Code Details
INV Port Temp=
—
INV Fin Temp=
—
INV Amps=
—
Ctrl Card Tmp=
—
Heatsink Tmp=
—
Refrig Circuit Status
PTD=
—
PTS=
—
4 WayValve=
—
RcvrSol Valve=
—
BP Sol Valve=
—
OM 1263 • MICROTECH UNIT CONTROLLER
Range
Password Level
Off
Start
Init
4
Normal
Pumpdn
Standby
Off
Start
Init
4
Normal
Pumpdn
Standby
0 – 100%
4
0 – 100%
4
Open
2
Closed
Off
4
On
-50 .0 – 200 .0°F
2
-50 .0 – 200 .0°F
2
0 – 50A
4
-50 .0 – 200 .0°F
2
-50 .0 – 200 .0°F
2
0 – 5000kPa
4
0 – 5000kPa
4
Cool
2
Heat
Closed
2
Open
Closed
2
Open
Item Display
Default Setting
Name
Compressor Setup
Clg Stg Time=
5min
55°F (RTU/SCU)
Clg Lo OAT Lk=
0°F (MPS)
25°F (DPS)
Clg OAT Diff=
2°F
0°F
Htg Lo OAT Lk=
45°F (100% OA
w/o ER)
Htg Hi OAT Lk=
55°F
EffHtgHiOATLk=
—
Htg OAT Diff=
2°F
INV Period=
20s
INV Gain=
2
INV PAT=
60s
INV Max Chg=
15%
OilManagement=
Off
LowOilTime=
10m
OilBoostTime=
10m
VFD Status=
—
VFD Alm/Wrn=
—
IFB Comm Status (10010)
24
Commission Unit
Range
Password Level
3 – 60min
4
0 – 100°F
4
0 – 10°F
4
-20 – 50°F
4
0 – 100°F
4
0 – 100°F
4
0 – 10°F
4
1 – 300s
4
0 .0 – 100 .0
4
0 – 999s
4
0 – 50%
4
Off
Balance
LoBoost
2
HiBoost
Boost
1 – 30m
2
1 – 15m
2
OK
OvrTActv
WrnActv
AlmNoTrp
2
AlmTrp
TripLck
NoComm
None
2
A** – W**
www .DaikinApplied .com