Controller Operation; Microtech Inputs/Outputs; Extension I/O Compressor #1 To #3 - Daikin MICROTECH III Operating Manual

Water-cooled screw chiller
Hide thumbs Also See for MICROTECH III:
Table of Contents

Advertisement

6

CONTROLLER OPERATION

6.1

MicroTech Inputs/Outputs

The chiller may be equipped with one up to three compressors.
6.1.1
Analog Inputs
#
Description
AI1
Evaporator Entering Water Temp
AI2
Evaporator Leaving Water Temp
AI3
Condenser Entering Water Temp
X1
Condenser Leaving Water Temp
X4
LWT Reset
X7
Demand Limit
X8
Unit Current
6.1.2
Analog Outputs
#
X5
Condenser Pump VFD
X6
Condenser Bypass Valve
6.1.3
Digital Inputs
#
DI1
Unit PVM
DI2
Evaporator Flow Switch
DI3
Double Set Point/ Mode Switch
DI4
External Alarm
DI5
Unit Switch
DI6
Emergency Stop
X2
Current Limit Enable
X3
Condenser Flow Switch
6.1.4
Digital Outputs
#
DO1
Evaporator Water Pump #1
DO2
Unit Alarm
DO3
Cooling Tower Out 1
DO4
Cooling Tower Out 2
DO5
Cooling Tower Out 3
DO6
Cooling Tower Out 4
DO7
DO8
Evaporator Water Pump #2
DO9
Condenser Water Pump
6.2

Extension I/O Compressor #1 to #3

6.2.1
Analog Inputs
#
Description
X1
Discharge Temperature
X2
Evaporator Pressure
X3
Oil Pressure
X4
Condenser Pressure
D–EOMWC00A07-16_02EN
Description
Description
Description
Signal Source
NTC Thermister (10K@25°C)
NTC Thermister (10K@25°C)
NTC Thermister (10K@25°C)
NTC Thermister (10K@25°C)
4-20 mA Current
4-20 mA Current
4-20 mA Current
Output Signal
0-10VDC
0-10VDC
Signal Off
Fault
No Flow
Cool mode
Remote off
Unit off
Unit off/rapid stop
Disabled
No Flow
Output OFF
Pump Off
Alarm not Active
Fan Off
Fan Off
Fan Off
Fan Off
Pump Off
Pump Off
Signal Source
NTC Thermister (10K@25°C)
Ratiometric (0,5-4,5 Vdc)
Ratiometric (0,5-4,5 Vdc)
Ratiometric (0,5-4,5 Vdc)
Operation Manual
Expected Range
-50°C – 120°C
-50°C – 120°C
-50°C – 120°C
-50°C – 120°C
1 to 23 mA
1 to 23 mA
1 to 23 mA
Range
0 to 100% (1000 steps resolution)
0 to 100% (1000 steps resolution)
Signal On
No Fault
Flow
Ice mode
Remote on
Unit on
Unit on
Enabled
Flow
Output ON
Pump On
Alarm Active (Flashing=
circuit alarm)
Fan On
Fan On
Fan On
Fan On
Pump On
Pump On
Expected Range
-50°C – 120°C
0 to 5 Vdc
0 to 5 Vdc
0 to 5 Vdc
14/77